Installation
Alerton Microset™ II
Mounting
The Microset II is designed to be wall-mounted indoors, with dimensions ideal for mounting to a single-gang electrical box. Mount in a clean, dry location away from windows, air ducts, and other places where environmental factors may affect temperature and humidity readings.
Note | If you mount the Microset II on the interior of a outside wall, thoroughly insulate so outside air behind the sensor doesn't affect the sensor reading. |
Compliance with the Americans with Disabilities Act
Backplate mounting dimensions
Securing the Microset II to a surface
Caution | Do not crimp or kink the pigtail wires |
Remove the Microset II from the backplate
Wiring
Wire specifications
- Type: 18-22 AWG, shielded
- Length: ≤1000 ft
- Resistance: <12Ω
VLC wire connections and terminations
The Microset II has a three-conductor connection to the VLC.
Note | Do not run Microset II wire in the same conduit or next to building power cables. This can cause interference. If it is necessary to cross power cables, lay the wire at a right angle (90º). |