devices:microset:qref
Table of Contents
Quick Reference
Alerton Microset™ II
Mode IDs
Code | Mode |
---|---|
M1 | Office, no fan, occupied |
M2 | Office, no fan, unoccupied |
M3 | Office, no fan, ON/OFF |
M4 | Office, fan, occupied |
M5 | Office, fan, unoccupied |
M6 | Hotel, no fan, rented |
M7 | Hotel, no fan, vacant |
M8 | Hotel, fan, rented |
M9 | Hotel, fan, vacant |
Field Service Codes
Code | Data point | Meaning |
---|---|---|
UC. | AV-95 | Unoccupied cooling setpoint |
UH. | AV-96 | Unoccupied heating setpoint |
CO. | AV-93 | Cooling offset |
HO. | AV-94 | Heating offset |
HS. | AV-100 | Occupied heating setpoint |
CS. | AV-99 | Occupied cooling setpoint |
AL. | AV-97 | Override limit |
HI. | AV-91 | Setpoint high limit |
LO. | AV-92 | Setpoint low limit |
SP. | AV-90 | Occupant-selected space temperature setpoint |
SC. | n/a | Size, cooling—size of VAV cooling duct diameter in inches or cm |
SH. | n/a | Size, heating—size of VAV heating duct diameter in inches or cm |
CF. | n/a | Cold flow—the current airflow in the VAV box cold duct in cfm or lps |
HF. | n/a | Hot flow—the current airflow in the VAV box hot duct, in cfm or lps |